ENGINEERING SPECIFICATION |
|
Model
OSD1P-3 Oil Smart Duplex System
|
|
Oil Smart Sump Pump System
Contractor shall furnish and
install See Water Oil Smart®
Duplex Panel Pump System or
approved equal. Sump Pump System
shall be capable of pumping water
without the risk of pumping oil.
The system shall automatically
function as Oil Containment system
relying on no moving parts. Pump
Control shall automatically
control pump to discharge water
without pumping oil, while
separate alarm on independent 120
VAC alarm circuit shall alarm and
differentiate in the event of high
oil or high water condition.
-
The Duplex Model # OSD1P-3 Panel
consists of the Oil Smart Water
Pump Controller with “on” and
“off” specific pumping range,
High Water 2 Pump Demand Switch
and Liquid Smart Switch to
detect high liquid level and
differentiate between oil and
water. The controls shall both
be able to differentiate between
oil and water and consist of no
moving parts.
-
The wall-mount NEMA 4X, UL and
CSA approved control panel shall
feature visible, full-alarm and
pump control capabilities
featuring pump run, pump fault
(no load lockout, pump seal
failure) indicator, high liquid
level, high water level and high
oil level with auxiliary
contacts for remote monitoring.
HOA (Hands-Off-Auto) Switch
shall be provided for manual
pump operation. Control panel
shall alternate between pumps
each pump cycle in normal
operation and in high demand
situations both pumps shall be
activated.
-
The system shall be combined
with two Single Phase,
110/208/240 VAC effluent
submersible pump and check
valves.
|
|
Model
OSD1P-3 (Click For More
Information)
|
| |
|
|
|